The EAE PS640 KNX Power Supply delivers stable, SELV-compliant power to a KNX installation from a mains supply. It provides up to 640 mA on the primary KNX output — suitable for medium to large KNX lines — plus a second 30 V DC auxiliary output for devices that need a separate feed (touch panels, certain actuators) without a second mains-powered supply.
Output 1 feeds the KNX bus through an integrated choke, which is required for correct KNX physical-layer behaviour. Output 2 provides 30 V DC without a choke and must not be used to power a second independent KNX bus segment. Both outputs are short-circuit and overload protected. Three front-panel LEDs and a reset button support on-site diagnostics and controlled bus recovery.
Key Features — Dual 30 V DC Outputs
Output 1 — KNX Bus Power
- 640 mA KNX output: 30 V DC +1/−2 V SELV with integrated choke.
- Short-circuit protection: 1.5 A short-circuit current limit.
- Device capacity: Supports up to 64 standard KNX devices per segment, subject to actual consumption and line design.
Output 2 — Auxiliary Voltage
- 30 V DC auxiliary: SELV output without choke for auxiliary consumers.
- Typical loads: EAE Miola touch panels, certain visualization devices — per project design.
- Important: Do not use for a second KNX bus segment — use a dedicated KNX PSU per topology rules.
Diagnostics and Reset
- Power LED (green): Mains input and KNX output voltage OK.
- Overload LED (red): Overload or short-circuit on outputs.
- Reset button: Press and hold until reset LED lights — KNX bus off for approx. 20 seconds for commissioning recovery.
At a Glance
| Specification | Detail |
| Product type | KNX Power Supply — 640 mA with auxiliary output |
| Order code | PS640 (SMP PS640) |
| KNX output current | 640 mA (30 V DC, with choke) |
| Auxiliary output | 30 V DC (without choke) |
| Input voltage | 150–275 V AC, 50–60 Hz |
| Power consumption | 22 W (PS640) |
| Protection | Short-circuit and overload on both outputs |
| Dimensions (H × W × D) | 60 × 126 × 90 mm (7 MW) |
| Weight | 0.29 kg |
| Mounting | 35 mm DIN rail |
Full electrical ratings are listed under Technical Specifications. Datasheet, installation manual, user manual, and certificates are under Downloads.
Applications and KNX Integration
- Mid-to-large residential: Central supply for actuators, sensors, and visualization where 320 mA is insufficient.
- Commercial distribution boards: Floor or tenancy KNX supply with auxiliary feed for touch panels.
- Touch panel projects: Auxiliary output powers MIOLA 10″ or TD4 panels alongside the KNX bus segment.
- System segmentation: Extend lines with an EAE LC200 Line Coupler or connect IP via the IPR200 IP Router.
- Hotel GRMS: For integrated room PSU + Modbus, consider the EAE KMG103 Gateway instead of separate PS640 per room.
Choosing EAE Power Supplies
The PS640 is the high-current EAE supply with auxiliary output — choose it when total bus consumption exceeds 320 mA or when a 30 V DC auxiliary feed is needed. For smaller lines, EAE also offers the PS320 (320 mA). Both share the same dual-output design and DIN-rail form factor.