ABB KNX Switch Actuator 24-fold 10A
Order code: SAH/S24.10.7.1
Brand: ABB
€491,00

€297,00
Need help choosing the right gateway?
The ABB IPS/S 3.1.1 KNX IP Interface (order code 2CDG110177R0011) is the interface between KNX installations and IP networks. It uses the KNXnet/IP protocol so KNX devices can be programmed via LAN with ETS, and visualisation or other clients can access the bus. From ETS4 onwards, five tunneling servers are available for concurrent sessions.
The MDRC device occupies 2 modular spacings (2 MW) (approx. 36 × 90 × 64.5 mm, net weight 0.1 kg). Power is supplied via 12…30 V DC or PoE (IEEE 802.3af class 1) — typically from ISP/S8.1.1.1 or an auxiliary supply such as CP-D 24/2.5. The IP address can be fixed or assigned by DHCP. Commission with the ABB IPS/S 3.1.1 ETS application from Downloads.
IPS/S is a tunneling interface, not a line/area IP router. For secure tunneling choose IPS/S3.5.1. For line/area coupling over IP, see IPR/S3.1.1 / IPR/S3.5.1. For local USB commissioning at the panel, see USB/S1.2.
| Specification | Detail |
|---|---|
| Product type | KNX IP Interface — KNXnet/IP tunneling |
| Order code | IPS/S3.1.1 (2CDG110177R0011) |
| EAN | 4016779906517 |
| Tunneling servers | 5 (from ETS4) |
| Power supply | 12…30 V DC or PoE (IEEE 802.3af class 1) |
| Width / weight | 2 MW; approx. 0.1 kg |
| Protection | IP20 |
| Secure variant | IPS/S3.5.1 (KNXnet/IP Secure) |
Firmware update guidance and tunneling notes are among the ABB engineering documents under Downloads.